Ceiling Type EPA Filter (Aluminum Frame)
Ceiling Type EPA Filter (Aluminum Frame) is a compact air filter designed for clean rooms, controlled production areas and precision HVAC applications. It can be used as a final-stage filter or as a high-efficiency prefilter upstream of HEPA filters. The product is available in E10, E11 and E12 filtration classes.
EN 1822
ISO 29463
Aluminum Frame

What Is a Ceiling Type EPA Filter?
Ceiling type EPA filters are compact filters designed to provide high-efficiency particulate filtration in ventilation systems. Fine glass fiber filter media is arranged in a mini-pleat geometry. Hot-melt separators maintain consistent spacing between the pleats. As a result, the structure increases filtration surface area and supports uniform airflow across the filter.
The aluminum frame offers low weight, mechanical strength, a smooth surface and compatibility with terminal filter boxes. The connection between the filter media and frame is sealed with a two-component polyurethane compound. Furthermore, the filter can be configured with different surface protection and gasket options according to the application.
Filtration Process
Technical Specifications
| Filter Standard | EN 1822 and ISO 29463 | Maximum Operating Temperature | 80°C |
| Filter Class | E10, E11 and E12 | Surface Protection | Paint-coated aluminum sheet |
| Filter Media | High-quality glass fiber | Gasket | EPDM, gray EPDM, poured gasket and U gasket options |
| Frame Type | Aluminum | Sealant | Two-component polyurethane |
| Recommended Final Pressure Drop | 2 times the initial pressure drop, maximum 600 Pa | Separator | Hot-melt adhesive |
Product Coding System
| Filter Type | Filter Class | Frame | Pleat Height | Dimensions | Surface Protection | Gasket |
|---|---|---|---|---|---|---|
| AR Ceiling Type EPA Filter Aluminum Frame |
E10 E11 E12 |
A: Aluminum | 1: 50 mm 2: 65 mm 3: 75 mm 4: 85 mm 5: 90 mm 6: 100 mm 7: 125 mm |
Width × Height × Depth Example: 610 × 610 × 78 mm |
FW: No protection FC: Clean side FD: Dirty side FB: Both sides |
W: No gasket P: Poured gasket PP: Double-sided poured gasket E: EPDM EE: Double-sided EPDM C: Gray EPDM CC: Double-sided gray EPDM U: U gasket |
AR-E10-A-1-610-610-78-FC-P
Filter Depth Options
Model and Performance Table at 78 mm Depth
The following models show reference performance values for a 78 mm filter depth and 50 mm pleat height.
| Filter Model | EN 1822 | ISO 29463 | Dimensions W × H × D |
Filtration Area | Pleat Height | Nominal Airflow | Initial Pressure Drop |
|---|---|---|---|---|---|---|---|
| AR-E10-A-1-305-305-78-FC-P | E10 | — | 305 × 305 × 78 mm | 2.3 m² | 50 mm | 150 m³/h | 80 Pa |
| AR-E10-A-1-305-610-78-FC-P | E10 | — | 305 × 610 × 78 mm | 4.5 m² | 50 mm | 300 m³/h | 80 Pa |
| AR-E10-A-1-457-457-78-FC-P | E10 | — | 457 × 457 × 78 mm | 5 m² | 50 mm | 340 m³/h | 80 Pa |
| AR-E10-A-1-610-610-78-FC-P | E10 | — | 610 × 610 × 78 mm | 9 m² | 50 mm | 600 m³/h | 80 Pa |
| AR-E10-A-1-610-915-78-FC-P | E10 | — | 610 × 915 × 78 mm | 13.5 m² | 50 mm | 900 m³/h | 80 Pa |
| AR-E10-A-1-610-1220-78-FC-P | E10 | — | 610 × 1220 × 78 mm | 18 m² | 50 mm | 1,200 m³/h | 80 Pa |
| AR-E11-A-1-305-305-78-FC-P | E11 | ISO 15 E | 305 × 305 × 78 mm | 2.3 m² | 50 mm | 150 m³/h | 90 Pa |
| AR-E11-A-1-305-610-78-FC-P | E11 | ISO 15 E | 305 × 610 × 78 mm | 4.5 m² | 50 mm | 300 m³/h | 90 Pa |
| AR-E11-A-1-457-457-78-FC-P | E11 | ISO 15 E | 457 × 457 × 78 mm | 5 m² | 50 mm | 340 m³/h | 90 Pa |
| AR-E11-A-1-610-610-78-FC-P | E11 | ISO 15 E | 610 × 610 × 78 mm | 9 m² | 50 mm | 600 m³/h | 90 Pa |
| AR-E11-A-1-610-915-78-FC-P | E11 | ISO 15 E | 610 × 915 × 78 mm | 13.5 m² | 50 mm | 900 m³/h | 90 Pa |
| AR-E11-A-1-610-1220-78-FC-P | E11 | ISO 15 E | 610 × 1220 × 78 mm | 18 m² | 50 mm | 1,200 m³/h | 90 Pa |
| AR-E12-A-1-305-305-78-FC-P | E12 | ISO 25 E | 305 × 305 × 78 mm | 2.3 m² | 50 mm | 150 m³/h | 95 Pa |
| AR-E12-A-1-305-610-78-FC-P | E12 | ISO 25 E | 305 × 610 × 78 mm | 4.5 m² | 50 mm | 300 m³/h | 95 Pa |
| AR-E12-A-1-457-457-78-FC-P | E12 | ISO 25 E | 457 × 457 × 78 mm | 5.1 m² | 50 mm | 340 m³/h | 95 Pa |
| AR-E12-A-1-610-610-78-FC-P | E12 | ISO 25 E | 610 × 610 × 78 mm | 9 m² | 50 mm | 600 m³/h | 95 Pa |
| AR-E12-A-1-610-915-78-FC-P | E12 | ISO 25 E | 610 × 915 × 78 mm | 13.5 m² | 50 mm | 900 m³/h | 95 Pa |
| AR-E12-A-1-610-1220-78-FC-P | E12 | ISO 25 E | 610 × 1220 × 78 mm | 18 m² | 50 mm | 1,200 m³/h | 95 Pa |
Model and Performance Table at 150 mm Depth
The following models show reference performance values for a 150 mm filter depth and 125 mm pleat height.
| Filter Model | EN 1822 | ISO 29463 | Dimensions W × H × D |
Filtration Area | Pleat Height | Nominal Airflow | Initial Pressure Drop |
|---|---|---|---|---|---|---|---|
| AR-E10-A-7-305-305-150-FC-P | E10 | — | 305 × 305 × 150 mm | 4.5 m² | 125 mm | 150 m³/h | 35 Pa |
| AR-E10-A-7-305-610-150-FC-P | E10 | — | 305 × 610 × 150 mm | 9 m² | 125 mm | 300 m³/h | 35 Pa |
| AR-E10-A-7-610-610-150-FC-P | E10 | — | 610 × 610 × 150 mm | 18 m² | 125 mm | 600 m³/h | 35 Pa |
| AR-E10-A-7-610-1220-150-FC-P | E10 | — | 610 × 1220 × 150 mm | 36 m² | 125 mm | 1,200 m³/h | 35 Pa |
| AR-E11-A-7-305-305-150-FC-P | E11 | ISO 15 E | 305 × 305 × 150 mm | 4.5 m² | 125 mm | 150 m³/h | 45 Pa |
| AR-E11-A-7-305-610-150-FC-P | E11 | ISO 15 E | 305 × 610 × 150 mm | 9 m² | 125 mm | 300 m³/h | 45 Pa |
| AR-E11-A-7-610-610-150-FC-P | E11 | ISO 15 E | 610 × 610 × 150 mm | 18 m² | 125 mm | 600 m³/h | 45 Pa |
| AR-E11-A-7-610-1220-150-FC-P | E11 | ISO 15 E | 610 × 1220 × 150 mm | 36 m² | 125 mm | 1,200 m³/h | 45 Pa |
| AR-E12-A-7-305-305-150-FC-P | E12 | ISO 25 E | 305 × 305 × 150 mm | 4.5 m² | 125 mm | 150 m³/h | 60 Pa |
| AR-E12-A-7-305-610-150-FC-P | E12 | ISO 25 E | 305 × 610 × 150 mm | 9 m² | 125 mm | 300 m³/h | 60 Pa |
| AR-E12-A-7-610-610-150-FC-P | E12 | ISO 25 E | 610 × 610 × 150 mm | 18 m² | 125 mm | 600 m³/h | 60 Pa |
| AR-E12-A-7-610-1220-150-FC-P | E12 | ISO 25 E | 610 × 1220 × 150 mm | 36 m² | 125 mm | 1,200 m³/h | 60 Pa |
Application Areas
Product Advantages
Installation and Operating Guidelines
Filter box dimensions must be compatible with the filter frame and gasket configuration.
Uniform compression must be maintained around the gasket perimeter to prevent localized leakage.
The filter should be selected according to the nominal airflow values in the table and the available system pressure capacity.
Filter replacement should be determined by measured differential pressure and process conditions, not only by operating time.
Technical Selection and Classification Note
EPA-class filters are not classified at the same level as HEPA and ULPA filters. Their use as a final-stage filter or HEPA prefilter should be determined according to clean-room classification, process risk, particle limits and validation requirements.
Filter performance may vary according to filter class, dimensions, pleat height, filtration area, nominal airflow, face velocity, installation sealing, particle loading and process conditions. Since an ISO 29463 equivalent for the E10 models is not specified in the source performance table, the final selection should be verified using the product datasheet and test documentation before ordering.
Get Technical Support for EPA Filter Selection