Deep Pleated High Capacity HEPA Filter (MDF Frame)
Deep Pleated High Capacity HEPA Filter (MDF Frame) is an absolute filtration solution developed for hygienic air handling units and controlled environments that require high airflow rates.
Available with nominal airflow capacities of 2,000 m³/h and 3,000 m³/h at 610 × 610 × 292 mm, the filter uses high-quality glass fibre media, hot-melt separators and a polyurethane sealing compound. Moreover, it can be configured in E10, E11, E12, H13, H14 and U15 classes.

What Is a Deep Pleated High Capacity HEPA Filter?
Deep pleated high capacity HEPA filters are designed with a large filtration area so that they can handle higher airflow rates than conventional absolute filters. The deep pleat geometry also helps distribute the air velocity evenly across the filter media.
The MDF frame provides an economical and lightweight housing option for disposable filter applications. The connection between the glass fibre filter media and MDF frame is sealed with a polyurethane compound. Depending on the application, face protection can be installed on the clean side, dirty side or both sides.
E10, E11 and E12 belong to the EPA category, while H13 and H14 are HEPA classes. U15 belongs to the ULPA category. Therefore, the appropriate filter class should be selected according to the particulate control requirements of the process and the system validation criteria.
Selection and Application Process
Applications
- Final-stage filtration in hygienic air handling units
- Pharmaceutical production facilities
- Hospitals and healthcare facilities
- Food production and packaging areas
- Laboratories and controlled-environment systems
- Biotechnology and precision manufacturing areas
Key Features
- 2,000 or 3,000 m³/h capacity at 610 × 610 × 292 mm
- Disposable MDF frame construction
- High-quality glass fibre filter media
- Large filtration area
- Optimised air velocity distribution
- Different gasket options
- Optional face protection
Technical Specifications
| Filter standard | EN 1822 and ISO 29463 | Maximum operating temperature | 80°C |
|---|---|---|---|
| Filter classes | E10, E11, E12, H13, H14 and U15 | Sealing compound | Polyurethane |
| Filter media | High-quality glass fibre | Separator | Hot melt |
| Frame type | MDF | Gasket options | EPDM, grey EPDM and poured gasket |
| Recommended final pressure drop | 2 × initial pressure drop, maximum 600 Pa | Face protection | Optional; clean side, dirty side or both sides |
Product Coding System
| Filter Model / Type | Filter Class | Frame | Capacity | Dimensions | Face Protection | Gasket |
|---|---|---|---|---|---|---|
| AR: Deep Pleated High Capacity HEPA Filter |
E10 E11 E12 H13 H14 U15 |
M: MDF | 20: 2,000 m³/h 30: 3,000 m³/h |
W × H × D Example: 610 × 610 × 292 mm |
FW: None FC: Clean side FD: Dirty side FB: Both sides |
W: None P: Poured gasket PP: Double-sided poured gasket E: EPDM EE: Double-sided EPDM C: Grey EPDM CC: Double-sided grey EPDM |
AR-H14-M-30-610-610-292-FC-E
M20 Capacity Deep Pleated High Capacity HEPA Filter
MDF-framed filter models with a nominal capacity of 2,000 m³/h at the full-module size of 610 × 610 × 292 mm.
| Filter Model | EN 1822 | ISO 29463 | Dimensions W × H × D (mm) |
Filtration Area (m²) |
Pleat Height (mm) |
Nominal Airflow (m³/h) |
Initial Pressure Drop (Pa) |
|---|---|---|---|---|---|---|---|
| AR-H13-M-20-287-592-292-FC-E | H13 | ISO 35 H | 287 × 592 × 292 | 8.5 | 125 | 940 | 240 |
| AR-H13-M-20-305-610-292-FC-E | H13 | ISO 35 H | 305 × 610 × 292 | 9 | 125 | 1,000 | 240 |
| AR-H13-M-20-592-592-292-FC-E | H13 | ISO 35 H | 592 × 592 × 292 | 17 | 125 | 1,880 | 240 |
| AR-H13-M-20-610-610-292-FC-E | H13 | ISO 35 H | 610 × 610 × 292 | 18 | 125 | 2,000 | 240 |
| AR-H14-M-20-287-592-292-FC-E | H14 | ISO 45 H | 287 × 592 × 292 | 9.4 | 125 | 940 | 270 |
| AR-H14-M-20-305-610-292-FC-E | H14 | ISO 45 H | 305 × 610 × 292 | 10 | 125 | 1,000 | 270 |
| AR-H14-M-20-592-592-292-FC-E | H14 | ISO 45 H | 592 × 592 × 292 | 18.8 | 125 | 1,880 | 270 |
| AR-H14-M-20-610-610-292-FC-E | H14 | ISO 45 H | 610 × 610 × 292 | 20 | 125 | 2,000 | 270 |
Production in special dimensions may be evaluated. The initial pressure drop tolerance is ±10%.
M30 Capacity Deep Pleated High Capacity HEPA Filter
MDF-framed filter models with a nominal capacity of 3,000 m³/h at the full-module size of 610 × 610 × 292 mm.
| Filter Model | EN 1822 | ISO 29463 | Dimensions W × H × D (mm) |
Filtration Area (m²) |
Pleat Height (mm) |
Nominal Airflow (m³/h) |
Initial Pressure Drop (Pa) |
|---|---|---|---|---|---|---|---|
| AR-H13-M-30-287-592-292-FC-E | H13 | ISO 35 H | 287 × 592 × 292 | 12.3 | 150 | 1,415 | 270 |
| AR-H13-M-30-305-610-292-FC-E | H13 | ISO 35 H | 305 × 610 × 292 | 13 | 150 | 1,500 | 270 |
| AR-H13-M-30-592-592-292-FC-E | H13 | ISO 35 H | 592 × 592 × 292 | 24.5 | 150 | 2,830 | 270 |
| AR-H13-M-30-610-610-292-FC-E | H13 | ISO 35 H | 610 × 610 × 292 | 26 | 150 | 3,000 | 270 |
| AR-H14-M-30-287-592-292-FC-E | H14 | ISO 45 H | 287 × 592 × 292 | 14.1 | 150 | 1,415 | 300 |
| AR-H14-M-30-305-610-292-FC-E | H14 | ISO 45 H | 305 × 610 × 292 | 15 | 150 | 1,500 | 300 |
| AR-H14-M-30-592-592-292-FC-E | H14 | ISO 45 H | 592 × 592 × 292 | 28.2 | 150 | 2,830 | 300 |
| AR-H14-M-30-610-610-292-FC-E | H14 | ISO 45 H | 610 × 610 × 292 | 30 | 150 | 3,000 | 300 |
Production in special dimensions may be evaluated. The initial pressure drop tolerance is ±10%.
Structural Components and Options
Provides an economical and lightweight housing solution for disposable filter applications.
Used to provide high particle retention performance in EPA, HEPA and ULPA classes.
Helps maintain pleat spacing and distribute airflow across the filter surface.
Applied to seal the connection between the filter media and the frame.
EPDM, grey EPDM and poured gasket alternatives can be selected according to the filter housing.
Can be applied on one or both sides to protect the filter media against mechanical contact.
Product Advantages
- High airflow options of 2,000 and 3,000 m³/h
- Large filtration area
- Balanced air velocity distribution
- H13 and H14 HEPA class options
- E10, E11, E12 and U15 alternatives
- Economical MDF frame construction
- Disposable product design
- Different gasket options
- Optional face protection
- Custom dimension production option
Product Selection Criteria
- Required E10, E11, E12, H13, H14 or U15 class
- Design airflow per filter
- M20 or M30 capacity selection
- Permissible initial and final pressure drop
- Clear installation dimensions of the filter housing
- Filter installation orientation and airflow direction
- Gasket type and compression surface
- Face protection requirement
- Prefilter class and system dust load
- Ambient temperature and relative humidity
- Test certificate and validation requirements
Maintenance and Replacement Criteria
The filter pressure drop should be monitored regularly and compared with the initial commissioning value.
The gasket surface, compression components and gaps in the filter housing should be checked during replacement.
Timely replacement of prefilters reduces the dust load and pressure increase across the HEPA filter.
The MDF-framed product is disposable and should not be cleaned and reused at the end of its service life.
The nominal airflow and initial pressure drop values shown in the tables refer to reference test conditions. Actual performance may vary depending on filter installation, test area, system static pressure, filter housing and duct leakage, airflow rate, measuring instrument calibration, dust load on the filter, temperature, relative humidity and process conditions. Therefore, filter selection should not be based only on nominal airflow. Fan capacity, total system pressure drop, prefiltration level, filter housing tightness and validation requirements should also be evaluated together.
High Capacity HEPA Filter Selection with MDF Frame
Contact Airtes for the selection of a high capacity HEPA filter with an MDF frame that matches your required filter class, design airflow, air handling unit dimensions and permissible pressure drop.