Floor Convectors
Aesthetic and High-Efficiency In-Floor Heating Solutions That Reduce Condensation on Large Glass Facades
Floor Convectors are in-floor heating units used to reduce cold downdrafts in front of large glazed areas, help prevent condensation on glass surfaces and provide comfortable heat distribution indoors.
Natural convection, fan-assisted and mini fan options meet different capacity needs. Depending on architectural requirements, they can be supplied with anodized aluminium, painted aluminium or timber linear grille options.

Natural / Fan-Assisted / Mini Fan
A natural convection, fan-assisted or mini fan model can be selected according to the required capacity.
Glass Facade Comfort
Helps reduce cold downdrafts and condensation risk on large glazed areas.
Production up to 6 Metres
Floor convectors can be manufactured in a single length of up to 6 metres according to project requirements.
What Is a Floor Convector?
A floor convector is a heating unit installed within the floor that distributes heat in a space through convection. It is particularly preferred for large glass facades, shop windows, lobby areas, offices, hotels, conservatories and spaces where visible radiators are not architecturally desired.
The system operates with a convector casing, heat exchanger, linear grille, frame, connection components and, in fan-assisted models, a low-noise fan assembly. Warm air movement at floor level creates a thermal curtain effect in front of the glass surface, improving comfort.
Floor Convectors Operating Principle
Cold Air Intake
Cold air formed in front of the glass surface is directed towards the convector channel.
Heat Exchanger
The heat exchanger supplied by the hot-water circuit heats the air passing through the convector.
Convection Effect
The heated air rises and forms a warm air curtain in front of the glass surface.
Controlled Comfort
In fan-assisted models, capacity can be managed automatically or manually through fan speed and valve control.
Key Technical Features
HYK-C natural convection, HYK-FC fan-assisted and HYK-MFC mini fan floor convectors.
85 mm and 115 / 116 mm casing height options.
Single-piece production of up to 6 metres according to project requirements.
Anodized aluminium, painted aluminium or timber linear grille.
Digital control panel, room thermostat, motorized valve and fan speed control.
Unnecessary capacity use can be reduced through fluid control valves and fan stages.
Floor Convector Types
| Model | Type | Operating Structure | Application Note |
|---|---|---|---|
| HYK-C | Natural Convection Floor Convector | Operates through natural airflow without a fan. | Suitable for quiet operation, low capacity needs and architectural comfort applications. |
| HYK-FC | Fan-Assisted Floor Convector | Airflow is increased by a tangential fan. | Preferred for glass facade applications requiring higher heating capacity. |
| HYK-MFC | Mini Fan Floor Convector | Provides heating at low casing height through a compact fan-assisted structure. | Suitable for areas with compact floor details and a need for fan-assisted capacity. |
Control and Accessories Table
| Accessory | Technical Feature | Purpose of Use |
|---|---|---|
| Room Panel and Controller | Electronic control board with 230 V power input; controls the motorized valve and fan speed in 3–5 stages. | Used for weekly scheduling and connection to building automation. |
| Digital Room Thermostat | Provides on/off motorized valve and single-stage fan control in fan-assisted or fanless applications. | Manages convector operation according to room temperature. |
| Two-Way Valve with Electrothermal Actuator | Can be used at a maximum water temperature of 95°C and pressure of 16 bar; operates on 230 V power. | Controls water flow according to the on/off signal from the thermostat. |
HYK-C Natural Convection Floor Convector Capacity Table
The table below is simplified from the HYK-C natural convection floor convector capacity table. The catalogue lists capacity values for C11-C32 types at different supply and return water temperatures and an ambient temperature of 20°C.
| Casing Length (L mm) |
C11 200×85 90-70°C |
C21 245×85 90-70°C |
C31 345×85 90-70°C |
C12 200×116 90-70°C |
C22 245×116 90-70°C |
C32 345×116 90-70°C |
C11 200×85 55-40°C |
C21 245×85 55-40°C |
C31 345×85 55-40°C |
C32 345×116 55-40°C |
|---|---|---|---|---|---|---|---|---|---|---|
| 1000 | 201 | 307 | 447 | 290 | 423 | 614 | 86 | 134 | 197 | 279 |
| 1500 | 324 | 509 | 767 | 512 | 701 | 1109 | 148 | 225 | 321 | 484 |
| 2000 | 477 | 796 | 965 | 739 | 1002 | 1483 | 208 | 325 | 402 | 647 |
| 2500 | 620 | 886 | 1143 | 933 | 1339 | 1712 | 256 | 364 | 476 | 777 |
| 3000 | 688 | 1018 | 1534 | 1074 | 1502 | 2218 | 296 | 450 | 642 | 968 |
| 4000 | 954 | 1592 | 1930 | 1478 | 2004 | 2966 | 416 | 650 | 804 | 1294 |
HYK-FC Fan-Assisted Floor Convector Capacity Table
The HYK-FC fan-assisted floor convector table includes FC11, FC21, FC31, FC12, FC22 and FC32 types, with convector dimensions of 245×116, 345×116 and 415×116 mm and fan airflow rates of 180 / 300 m³/h.
| Casing Length (L mm) |
FC11 245×116 90-70°C |
FC21 345×116 90-70°C |
FC31 415×116 90-70°C |
FC12 245×116 90-70°C |
FC22 345×116 90-70°C |
FC32 415×116 90-70°C |
FC11 245×116 55-40°C |
FC21 345×116 55-40°C |
FC31 415×116 55-40°C |
FC32 415×116 55-40°C |
|---|---|---|---|---|---|---|---|---|---|---|
| 1250 | 651 / 995 | 996 / 1547 | 1192 / 1883 | 1326 / 2054 | 1738 / 2825 | 1964 / 3268 | 291 / 376 | 459 / 731 | 573 / 913 | 969 / 1614 |
| 2000 | 1272 / 1923 | 1732 / 2716 | 2011 / 3212 | 2292 / 3618 | 2862 / 4726 | 3176 / 5365 | 595 / 912 | 846 / 1329 | 988 / 1584 | 1578 / 2667 |
| 2500 | 1746 / 2635 | 2340 / 3666 | 2702 / 4314 | 3093 / 4885 | 3835 / 6335 | 4245 / 7177 | 840 / 1275 | 1151 / 1806 | 1338 / 2137 | 2114 / 3571 |
| 3500 | 2314 / 3462 | 3232 / 5023 | 3784 / 5995 | 4284 / 6675 | 5442 / 8894 | 6084 / 10180 | 1055 / 1617 | 1566 / 2447 | 1858 / 2949 | 3021 / 5055 |
| 4500 | 3280 / 4911 | 4457 / 6939 | 5174 / 8216 | 5901 / 9231 | 7400 / 12125 | 8232 / 13702 | 1565 / 2358 | 2186 / 3410 | 2556 / 4063 | 4095 / 6871 |
Note: In the fan-assisted model values, the first value in each cell corresponds to 180 m³/h fan airflow and the second value corresponds to 300 m³/h fan airflow.
HYK-MFC Mini Fan Floor Convector Capacity Table
The HYK-MFC mini fan model table includes MFC11, MFC21 and MFC31 types with convector dimensions of 220×85, 300×85 and 380×85 mm. Heating capacities are listed for water temperatures of 90-70°C, 80-60°C, 70-55°C and 55-40°C.
| Casing Length (L mm) |
MFC11 220×85 90-70°C |
MFC21 300×85 90-70°C |
MFC31 380×85 90-70°C |
MFC11 220×85 70-55°C |
MFC21 300×85 70-55°C |
MFC31 380×85 70-55°C |
MFC11 220×85 55-40°C |
MFC21 300×85 55-40°C |
MFC31 380×85 55-40°C |
|---|---|---|---|---|---|---|---|---|---|
| 1250 | 597 | 928 | 1104 | 403 | 622 | 761 | 285 | 416 | 526 |
| 2000 | 1435 | 1958 | 2274 | 977 | 1366 | 1597 | 672 | 955 | 1120 |
| 2500 | 1642 | 2174 | 2494 | 1133 | 1524 | 1756 | 787 | 1069 | 1234 |
| 3500 | 2535 | 3301 | 3768 | 1769 | 2324 | 2660 | 1239 | 1634 | 1872 |
| 4500 | 3092 | 4146 | 4782 | 2120 | 2900 | 3364 | 1468 | 2032 | 2362 |
Electrical Power of Fan-Assisted Models
Fan-assisted and mini fan floor convectors operate on 230 V voltage. The catalogue provides power values according to fan speed for HYK-FC fan-assisted models and according to casing length for HYK-MFC mini fan models.
| Casing Length (L mm) |
HYK-FC 750 rpm Power (W) |
HYK-FC 1500 rpm Power (W) |
HYK-MFC Power (W) |
|---|---|---|---|
| 1250 | 35 | 52 | 21 |
| 1500 | 35 | 52 | 21 |
| 2000 | 70 | 104 | 42 |
| 2500 | 70 | 104 | 42 |
| 2750 | 105 | 156 | 42 |
| 3500 | 105 | 156 | 63 |
| 4000 | 105 | 156 | 84 |
| 4500 | 140 | 208 | 84 |
Material, Surface and Grille Options
| Item | Description |
|---|---|
| Linear grille | High-strength aluminium profile; anodized, painted or timber-look options according to architectural preference. |
| Convector casing | High-strength aluminium profile structure; casing design suitable for recessed floor installation. |
| Frame | Anodized aluminium linear grille and frame as standard; optional RAL colour choice. |
| Fan control | The fan can be controlled automatically or manually in 3 stages. |
| Building automation | The controller operates with a room control panel; weekly scheduling and building automation connection are possible. |
Application Areas
Application Note
When selecting a floor convector, glass facade length, heat loss, water regime, required capacity, casing height, floor detail, fan-assisted / fanless operation need, sound level, grille type, control scenario and building automation integration should be evaluated together.
Get Technical Support for Floor Convector Selection
Floor convector selection should be based on heating capacity, glass facade dimensions, casing height, fan-assisted or natural convection operating type, water regime, grille type and control requirement.
You can request a project-specific technical assessment for floor convector selection in large glass facades, lobby areas, showrooms and architectural comfort applications.